Shenzhen Zhide Cable Technology Co., Ltd.
Description









|
Photovoltaic Cable H1Z2Z2K
|
|||||
|
Nominal Area
(m㎡)
|
Approx. Diam(m㎡)
|
Insulation Thickness(m㎡)
|
Sheath
Thickness(m㎡)
|
Cable
Diam(mm)
|
Maximum Resistance
20°C (Ω/Km)
|
|
1×1.5
|
1.57
|
0.7
|
0.8
|
4.7
|
13.7
|
|
1×2.5
|
2.04
|
0.7
|
0.8
|
5.2
|
8.21
|
|
1×4
|
2.6
|
0.7
|
0.8
|
5.6
|
5.09
|
|
1×6
|
3.16
|
0.7
|
0.8
|
6.3
|
3.39
|
|
1×10
|
4.5
|
0.7
|
0.8
|
7.6
|
1.95
|
|
1×16
|
5.7
|
0.7
|
0.9
|
9.0
|
1.24
|
|
1×25
|
7.2
|
0.9
|
1.0
|
11.2
|
0.795
|
|
1×35
|
8.5
|
0.9
|
1.1
|
12.7
|
0.565
|
|
1×50
|
9.4
|
1.0
|
1.2
|
14.5
|
0.393
|
|
1×70
|
11.1
|
1.1
|
1.2
|
16.5
|
0.277
|
|
1×95
|
13.1
|
1.1
|
1.3
|
18.7
|
0.210
|
|
1×120
|
14.8
|
1.2
|
1.3
|
20.4
|
0.164
|
|
2×1.5
|
1.57
|
0.7
|
0.8
|
4.8—10.5
|
13.7
|
|
2×2.5
|
2.04
|
0.7
|
0.8
|
5.2—11.8
|
8.21
|
|
2×4
|
2.6
|
0.7
|
0.8
|
5.6—12.8
|
5.09
|
|
2×6
|
3.16
|
0.7
|
0.8
|
6.3—13.7
|
3.39
|
|
2×10
|
4.5
|
0.7
|
0.8
|
8.0—16.8
|
1.95
|
|
2×16
|
5.7
|
0.7
|
0.8
|
9.0—19.8
|
1.24
|
Electrical Performance
Low voltage: 1,5 (1,8) kV DC; 1,0/1,0 kV AC.
Thermal Performance
Maximum conductor temperature: 90°C (120°C during 20.000 h).
Maximum short-circuit temperature: 250°C (max.5 s).
Minimum service temperature: -40°C (fixed and protected installations).
Fire Performance
Flame non-propagation according to EN 60332-1+-2 / IEC 60332-1-2.
Fire non-propagation according to EN 50399.
Reaction to fire CPR: Ca-s1b, d2, al according to EN 50575.
Low smoke halogen free according to EN 60754-1 / IEC 60754-1.
Low corrosive gases emission according to EN 60754-2 / IEC 60754-2.
Low smoke emission according to EN 61034 / IEC 61034.
Light transmittance> 60%.
Mechanical Performance
Minimum bending radius: 4x cable diameter (cable diameter≤8 mm)
5x cable diameter (8 < cable diameter s 12 mm)
6x cable diameter (cable diameter > 12 mm)
Ilmpact resistance: AG2 Medium severity.
Environmental Performance
Chemical & Oil resistance: Excellent.
Grease & mineral oils resistance: Excellent.
Ozone resistant according to EN 50618.
UV Resistant according to EN 50618 and IEC 62930.
Water resistance: AD7+ Immersion. AD8 Submersion.
Installation Conditions
Open Air. Buried. In conduit.
Constriction
Conductor:Electrolytic annealed tinned copper, class 5 (flexible) according to IEC 60228 and EN 60228.
Insulation:Halogen free cross-linked rubber according to table B1 in Annex B of EN 50618 and IEC 62930.
Outer sheath:Halogen free cross-inked flexible rubber according to table B1 in Annex B of EN 50618 and IEC 62930.